Modulating Fire/Smoke Dampers – Three Dampers in ONE!

Wednesday, June 6, 2007


Question:  How do you get three dampers for the price of one? 

Answer: Use a modulating combination fire/smoke damper from Ruskin. 

1.    First, they are a fire damper that closes automatically upon detection of heat, resists the passage of flame and maintains the integrity of the fire rated separation. 

2.    Second, they are a smoke damper that closes when signaled by a smoke detector and provides low leakage protection for air and smoke. 

3.    Third, they are a volume control damper.  That’s right, a control damper; and a UL approved one at that.  Let’s find out how.

Realizing the need for smoke/isolation protection in return air paths for air systems over 15,000 cfm, the question is how do you regulate the airflow at the same time?  The answer is Ruskin FSD60M and SD60M dampers with modulating actuators.

Tougher Underwriters Laboratories (UL) Testing

These 3-in-1 dampers are approved to a more stringent cycling test per UL555S. The test requires the fire/smoke damper and actuator assembly to operate 100,000 full-stroke operations.  That’s ten cycles a day for 27 years.  For comparison’s sake, the more common two-position fire/smoke dampers are tested to 20,000 cycles. Ruskin’s volume control UL dampers are UL555S Leakage Class 1 rated at 250oF and the FSD60M is also fire resistance rated for 1-1/2 or 3 hours in accordance with UL555.

Increased Applications

The use of volume control fire/smoke dampers has increased dramatically over the last few years as system designers recognize the cost savings and reduced space by combining the fire life safety damper and the control damper into a single unit. In addition, these 3-in-1 dampers are ideal for under-floor ventilation systems due to space limitations. 

Additional Certifications

Do your specifications call for AMCA certification for performance you can count on?  No problem.  Ruskin’s FSD60M, FSD60-3M and SD60M models are AMCA certified for air performance giving you the low pressure drop you need in your system.  The most specified UL damper in the industry also features:

·       FM Approval as a Specification Tested Products.

·       Production in ISO9001/2000 certified facilities.

To learn more about Ruskin’s complete line of dampers, louvers, air measuring and sound control products or to locate a Ruskin representative nearest you, visit our website at www.ruskin.com or call us at 816-761-7476.

 


 

Comments:
Manuel Vigil
Apr 21, 2009 1:21 PM
We have installed Ruskin SD60 Smoke dampers with a SIEBE MA-318-0-0-3 actuator. One of our techs replaced the SIEBE actuator with a Belimo. Does this meet UL listing for smoke control? Where/how do I find out if this is legal and should they have used a SIEBE actuator

Ruskin
Apr 22, 2009 8:18 AM
Not all Belimo actuators are approved for use with UL classified smoke dampers. The Belimo actuators that are approved are the FSLF, FSNF and FSAF actuators. The substitution you speak of should be okay as long as the damper is not modified. However, in order to be absolutely sure get the approval of the local authority having jurisdiction.

ken
Jun 21, 2009 8:16 PM
How do you determine wheather a fire smoke damper has a left hand or right hand motor.would it be looking at the air flow?

Ruskin
Jul 2, 2009 10:59 AM
The location of the actuator is determined not by airflow but by damper construction. The front of the damper is side where the jackshaft resides. The jackshaft is the 1/2" shaft that runs across the face of the damper. If you are viewing the damper from the front, the actuator is on the right side. Please know, however, some dampers may require actuators on both sides.