The FSD36FA Combination Fire/Smoke Damper is both UL555 and UL555S Classified. It is rated as a 1-1/2 hour fire damper and a Leakage Class II Smoke damper. It is specifically designed for supply or return ducts with grille outlet. It features:
- Rated to 2,000 fpm and 4" w.g.
- Through the grille access to damper and all accessories.
- Airfoil blades, which have greater strength, less static pressure, superior sealing ability, superior fire protection ability, and produce less noise.
- Failsafe design, which enables the damper to automatically assume the desired position when fire interrupts operational power.
- The EFL or PFL heat-actuated release devices permit controlled closure through the actuator and are automatically remote resettable after test, smoke detection, or power failure conditions.